Page 454 - 2015 Master Catalog
P. 454

SDR-480-48

480W/10A DIN-Rail 48VDC Industrial Power Supply

                    Features

                            •	 High efficiency 94% and low power dissipation
                            •	 UL508 (industrial control equipment) approved
                            •	 EN61000-6-2 (EN50082-2) industrial immunity level
                            •	 -25°C to 70°C operating temperature range

Hardware Specifications                                                  Over Temperature Protection
                                                                          •	105°C ± 5°C (TSW : detect on heatsink of power switch)
Power                                                                     •	Shut down o/p voltage, recovers automatically after

      Power Input                                                           temperature goes down
       •	Voltage Range: 90 to 240VAC or 127 to 370VDC
       •	Frequency Range: 47 to 63Hz                               Environmental
       •	Power Factor (Typ.): 0.94 / 230VAC;
       •	0.99 / 115VAC at full load                                      Operating Temperature
       •	Efficiency: 94%                                                  •	-25°C to 70°C (Refer to output load derating curve)
       •	AC Current (Typ.): 5A/115VAC; 2.5A/230VAC                       Storage Temperature
       •	Inrush Current (Typ.): 40A/115VAC; 80A/230VAC                    •	-40°C to 85°C (-40°F to 158°F)
       •	Leakage Current: <0.8mA / 240VAC                                Working Humidity
      Power Output                                                        •	20% to 90%RH non-condensing
       •	DC Voltage: 48V Rated Current: 10A                              Storage Humidity
       •	Current Range: 0 to 10A                                          •	10% to 95%RH
       •	Rated Power: 480W                                         Regulatory Approvals
       •	Peak Current 15A Peak Power: 720W (3sec.)
       •	Ripple & Noise (max.): 120mVp-p                                 Safety
       •	Voltage Tolerance: ± 1.0%                                        •	UL508
       •	Line Regulation: ± 0.5%                                          •	TUV EN60950-1
       •	Load Regulation: ± 1.0%                                         EMC
       •	Setup, Rise Time: 1500ms, 150ms/230VAC 3000ms,                   •	EN55022
                                                                          •	EN61000-3-2
                               150ms/115VAC at full load                  •	EN61000-3-3
       •	Hold up Time: 14ms/230VAC at full load                           •	Withstand Voltage

Mechanical                                                                   ◦◦ I/P-O/P:3KVAC
                                                                             ◦◦ I/P-FG:1.5KVAC
      Casing                                                                 ◦◦ O/P-FG:0.5KVAC
       •	Aluminum case                                                       ◦◦ O/P-DC OK:0.5KVAC
      Dimensions                                                          •	Isolation Resistance
       •	85.5mm (W) x 128.5mm (D) x 125.2 mm(H)                              ◦◦ I/P-O/P
                                                                             ◦◦ I/P-FG
         (3.42" (W) x 5.14" (D) x 5.01" (H))                                 ◦◦ O/P-FG:>100M Ohms / 500VDC / 25°C / 70% RH
      Weight                                                             EMS
       •	1.6kg (3.52 lb)                                                  •	EN61000-4-2,3,4,5,6,8,11 ENV50204 EN55024 EN61000-6-
      Installation                                                          2 (EN50082-2) EN61204-3 Heavy industry level, criteria A ,
       •	DIN-Rail                                                           SEMI F47 approved
    Protection                                                           Environmental Test Compliance
      Over Voltage Protection                                             •	IEC60068-2-6
       •	56 - 65V                                                            ◦◦ Component:10 to 500Hz, 2G 10min./1cycle, 60min. each
      Over Load Protection
       •	Normally works within 110 to 150% rated output power for              along X, Y, Z axes; mounting: Compliance to IEC60068-2-6

         more than 3 seconds and then shut down o/p voltage with
         auto-recovery

SDR-480-48                                                         42 www.EtherWAN.com